Fire doors and emergency lighting guide for property managers

A practical England-focused guide to managing fire doors, escape-route lighting, routine checks, maintenance evidence and the relationship with the fire risk assessment.

Start with the fire risk assessment

Fire doors and emergency escape lighting should not be managed as isolated certificate items. The fire risk assessment should identify the escape strategy, the fire-resisting doors that protect relevant routes and compartments, and whether emergency escape lighting is needed so people can reach a place of safety if normal lighting fails.

The Responsible Person must then make sure relevant precautions remain effective. That means keeping fire doors in good working order, addressing defects, maintaining escape routes and ensuring emergency lighting is tested and maintained where it is required.

Assess

Use the fire risk assessment to establish the required fire precautions, escape strategy and the role of doors, lighting, alarms and signage.

Inspect and test

Carry out the routine checks and competent-person inspection or testing appropriate to the building, system and identified risk.

Record and act

Keep evidence of checks, defects, remedial work and resident communication so the fire-safety management trail remains clear.

Fire-door checks in blocks of flats

The Fire Safety (England) Regulations 2022 introduced specific fire-door duties for multi-occupied residential buildings. In buildings where the top storey is more than 11 metres above ground level, the Responsible Person must use best endeavours to check flat entrance fire doors at least every 12 months and must check fire doors in communal areas at least every three months.

For blocks of flats with common parts, residents must also be given information about the importance of keeping fire doors shut when not in use, not tampering with self-closing devices and reporting faults or damage. This resident information requirement is broader than the routine-check requirement above 11 metres.

Routine checks are not the same as a fire-door assessment

Government guidance makes a clear distinction between the simple routine checks required under regulation 10 and the fire risk assessment that considers whether the fire performance of a door is adequate for the building. A routine check should identify obvious problems such as damage, poor closing, changes to the door, letterbox issues or defects affecting the door, frame or surrounding construction.

Where the suitability of a door is uncertain, the issue should be considered through competent fire-safety assessment rather than assuming that a door must automatically be replaced simply because it lacks modern certification, seals or markings. The current government guidance specifically cautions against that misunderstanding.

What to keep visible in a fire-door register

  • door location and type
  • whether it is a communal or flat-entrance door
  • latest routine-check date
  • condition of door, frame, glazing, ironmongery and self-closing device
  • identified damage or alteration
  • remedial action and completion date
  • evidence from any specialist assessment
  • resident-access attempts where annual flat entrance checks are required

When emergency escape lighting is needed

Under the Fire Safety Order, where escape routes and exits require artificial illumination, adequate emergency lighting must be provided where necessary. The fire risk assessment should therefore consider the building layout, occupancy, use in hours of darkness, internal or windowless routes and whether people could still find their way to safety if normal lighting failed.

In larger or more complex premises, automatic emergency escape lighting is commonly needed to illuminate routes, stairways, changes of level, exit doors, final exits and relevant fire-safety equipment. The exact design should follow the risk assessment and appropriate technical standards rather than a generic fitting count.

Testing and maintenance: use the right benchmark

Emergency lighting must be kept effective, tested and maintained. Government guidance for small non-domestic premises describes a monthly functional check and annual inspection and test by a competent contractor as a practical maintenance benchmark. This should not be treated as a universal statutory interval for every building; the maintenance regime should reflect the system, premises, risk assessment and applicable technical guidance.

Where a duration test, repair or system alteration is required, plan the work so the building is not left without the fire precautions it needs while batteries recover or equipment is out of service.

A joined-up management workflow

For each building, link the fire risk assessment to the fire-door register, emergency-lighting test records, alarm records, remedial actions and resident communications. If the fire risk assessment changes the escape strategy or identifies deficiencies, the corresponding inspection and maintenance schedules should be reviewed rather than left on an old cycle.

For portfolios, record the Responsible Person, building height where relevant, assessment review date, fire-door check dates, emergency-lighting test dates, defects and next actions against each property. This makes overdue work and unresolved defects much easier to identify.

Related Primelinks guidance and services

Use our Fire Risk Assessment Guide for the wider assessment framework. For operational work, see Fire Door Inspection, Emergency Lighting and Fire Risk Assessment.

This guide is a practical overview for England and is not a substitute for a building-specific fire risk assessment, competent technical advice or legal advice. Fire precautions depend on the premises, occupancy, escape strategy, building height and findings of the fire risk assessment.